Cyberex Digital Three Phase Charger 25-1000A
Current Ratings |
25, 30, 40, 50, 75, 100, 125, 150, 200, 250, 300, 400, 500, 600, 800, 1000 A |
Voltage |
208, 240, 480 or 550–600VAC 60Hz
220, 380, or 416VAC 50/60Hz |
Voltage range |
+10%, -12% |
Input Frequency Tolerance |
±5% |
Efficiency |
85-90% typical for 130VDC at 50-100% load |
Voltage ratings |
12, 24, 48, or 130 VDC nominal |
Continuous ratings |
110% rated current at maximum equalized voltage at 50º C |
Voltage regulation |
± 0.25% for line, load, frequency and temperature variations |
Electrical noise |
32dBrnc |
Ripple 12/24/48VDC |
– Unfiltered on battery 1% Vrms
– Filtered on battery 30mVrms
– Filtered off battery 1% Vrms
– Battery Eliminator 30mVrms |
130VDC: |
– Unfiltered on battery 2% Vrms
– Filtered on battery 100mVrms
– Filtered off battery 2% Vrms
– Battery Eliminator 100mVrms |
Surge Withstand Capability |
Meets IEEE-472/ANSI C37.90a |
User interface/indications |
Digital LED Meter |
Communication ports |
Modbus and Ethernet Communications ports available |
Operating ambient temperature |
0–122°C (-18º C to 50º C) without derating |
Operating altitude |
10,000 feet (3,000 meters) above sea level without derating load |
Relative humidity |
5-95% non-condensing |
Audible noise |
Less than 65 dBA at any point 5ft. (1.5m) from any vertical surface of enclosure |
Technical specifications are subject to change without notice.
Reviews